← Voltar para CVEs
CVE-2025-9041
N/ADescricao
A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.
Detalhes CVE
Pontuacao CVSS v3.1N/A
Publicado8/14/2025
Ultima modificacao8/15/2025
Fontenvd
Avistamentos honeypot0
Fraquezas (CWE)
CWE-1287
Referencias
https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1737.html(PSIRT@rockwellautomation.com)
Correlacoes IOC
Sem correlacoes registradas
This product uses data from the NVD API but is not endorsed or certified by the NVD.