Descricao

The Honeywell Experion PKS contains an Integer Underflow vulnerability in the component Control Data Access (CDA). An attacker could potentially exploit this vulnerability, leading to Input Data Manipulation, which could result in improper integer data value checking during subtraction leading to a denial of service. Honeywell recommends updating to the most recent version of Honeywell Experion PKS:520.2 TCU9 HF1 and 530.1 TCU3 HF1. The affected Experion PKS products are C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E. The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3.

Detalhes CVE

Pontuacao CVSS v3.18.2
SeveridadeHIGH
Vetor CVSSCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H
Vetor de ataqueNETWORK
ComplexidadeLOW
Privilegios necessariosNONE
Interacao do usuarioNONE
Publicado7/10/2025
Ultima modificacao7/15/2025
Fontenvd
Avistamentos honeypot0

Fraquezas (CWE)

CWE-191

Referencias

https://process.honeywell.com/(psirt@honeywell.com)