CVE-2025-2523

CRITICAL
9.4

Descricao

The Honeywell Experion PKS and OneWireless WDM contains an Integer Underflow vulnerability in the component Control Data Access (CDA). An attacker could potentially exploit this vulnerability, leading to a Communication Channel Manipulation, which could result in a failure during subtraction allowing remote code execution. Honeywell recommends updating to the most recent version of Honeywell Experion PKS:520.2 TCU9 HF1 and 530.1 TCU3 HF1 and OneWireless: 322.5 and 331.1. The affected Experion PKS products are C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E. The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3. The OneWireless WDM affected versions are 322.1 through 322.4 and 330.1 through 330.3.

Detalhes CVE

Pontuacao CVSS v3.19.4
SeveridadeCRITICAL
Vetor CVSSCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H
Vetor de ataqueNETWORK
ComplexidadeLOW
Privilegios necessariosNONE
Interacao do usuarioNONE
Publicado7/10/2025
Ultima modificacao7/15/2025
Fontenvd
Avistamentos honeypot0

Fraquezas (CWE)

CWE-191