← Voltar para CVEs
CVE-2022-40202
CRITICAL9.8
Descricao
The database backup function in Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior lacks proper authentication. An attacker could provide malicious serialized objects which, when deserialized, could activate an opcode for a backup scheduling function without authentication. This function allows the user to designate all function arguments and the file to be executed. This could allow the attacker to start any new process and achieve remote code execution.
Detalhes CVE
Pontuacao CVSS v3.19.8
SeveridadeCRITICAL
Vetor CVSSCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Vetor de ataqueNETWORK
ComplexidadeLOW
Privilegios necessariosNONE
Interacao do usuarioNONE
Publicado10/31/2022
Ultima modificacao11/21/2024
Fontenvd
Avistamentos honeypot0
Produtos afetados
deltaww:infrasuite_device_master
Fraquezas (CWE)
CWE-306
Referencias
https://www.cisa.gov/uscert/ics/advisories/icsa-22-298-07(ics-cert@hq.dhs.gov)
https://www.cisa.gov/uscert/ics/advisories/icsa-22-298-07(af854a3a-2127-422b-91ae-364da2661108)
Correlacoes IOC
Sem correlacoes registradas
This product uses data from the NVD API but is not endorsed or certified by the NVD.