TROYANOSYVIRUS
Voltar para CVEs

CVE-2019-14931

CRITICAL
9.8

Descricao

An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. An unauthenticated remote OS Command Injection vulnerability allows an attacker to execute arbitrary commands on the RTU due to the passing of unsafe user supplied data to the RTU's system shell. Functionality in mobile.php provides users with the ability to ping sites or IP addresses via Mobile Connection Test. When the Mobile Connection Test is submitted, action.php is called to execute the test. An attacker can use a shell command separator (;) in the host variable to execute operating system commands upon submitting the test data.

Detalhes CVE

Pontuacao CVSS v3.19.8
SeveridadeCRITICAL
Vetor CVSSCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Vetor de ataqueNETWORK
ComplexidadeLOW
Privilegios necessariosNONE
Interacao do usuarioNONE
Publicado10/28/2019
Ultima modificacao11/21/2024
Fontenvd
Avistamentos honeypot0

Produtos afetados

inea:me-rtuinea:me-rtu_firmwaremitsubishielectric:smartrtumitsubishielectric:smartrtu_firmware

Fraquezas (CWE)

CWE-78

Referencias

https://www.mogozobo.com/(af854a3a-2127-422b-91ae-364da2661108)
https://www.mogozobo.com/?p=3593(af854a3a-2127-422b-91ae-364da2661108)

Correlacoes IOC

Sem correlacoes registradas

This product uses data from the NVD API but is not endorsed or certified by the NVD.