CVE-2019-14926
CRITICAL9.8
Descricao
An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. Hard-coded SSH keys allow an attacker to gain unauthorised access or disclose encrypted data on the RTU due to the keys not being regenerated on initial installation or with firmware updates. In other words, these devices use private-key values in /etc/ssh/ssh_host_rsa_key, /etc/ssh/ssh_host_ecdsa_key, and /etc/ssh/ssh_host_dsa_key files that are publicly available from the vendor web sites.
Detalhes CVE
Pontuacao CVSS v3.19.8
SeveridadeCRITICAL
Vetor CVSSCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Vetor de ataqueNETWORK
ComplexidadeLOW
Privilegios necessariosNONE
Interacao do usuarioNONE
Publicado10/28/2019
Ultima modificacao11/21/2024
Fontenvd
Avistamentos honeypot0
Produtos afetados
inea:me-rtuinea:me-rtu_firmwaremitsubishielectric:smartrtumitsubishielectric:smartrtu_firmware
Fraquezas (CWE)