← Voltar para CVEs
CVE-2019-13553
CRITICAL9.8
Descricao
Rittal Chiller SK 3232-Series web interface as built upon Carel pCOWeb firmware A1.5.3 – B1.2.4. The authentication mechanism on affected systems is configured using hard-coded credentials. These credentials could allow attackers to influence the primary operations of the affected systems, namely turning the cooling unit on and off and setting the temperature set point.
Detalhes CVE
Pontuacao CVSS v3.19.8
SeveridadeCRITICAL
Vetor CVSSCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Vetor de ataqueNETWORK
ComplexidadeLOW
Privilegios necessariosNONE
Interacao do usuarioNONE
Publicado10/25/2019
Ultima modificacao11/21/2024
Fontenvd
Avistamentos honeypot0
Produtos afetados
carel:pcoweb_firmwarerittal:chiller_sk_3232
Fraquezas (CWE)
CWE-798CWE-798
Referencias
http://seclists.org/fulldisclosure/2019/Oct/45(ics-cert@hq.dhs.gov)
https://www.us-cert.gov/ics/advisories/icsa-19-297-01(ics-cert@hq.dhs.gov)
http://seclists.org/fulldisclosure/2019/Oct/45(af854a3a-2127-422b-91ae-364da2661108)
https://www.us-cert.gov/ics/advisories/icsa-19-297-01(af854a3a-2127-422b-91ae-364da2661108)
Correlacoes IOC
Sem correlacoes registradas
This product uses data from the NVD API but is not endorsed or certified by the NVD.