TROYANOSYVIRUS
Retour aux CVEs

CVE-2026-3611

CRITICAL
10.0

Description

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

Details CVE

Score CVSS v3.110.0
SeveriteCRITICAL
Vecteur CVSSCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
Vecteur d'attaqueNETWORK
ComplexiteLOW
Privileges requisNONE
Interaction utilisateurNONE
Publie3/12/2026
Derniere modification3/13/2026
Sourcenvd
Observations honeypot0

Faiblesses (CWE)

CWE-306

Correlations IOC

Aucune correlation enregistree

This product uses data from the NVD API but is not endorsed or certified by the NVD.