CVE-2023-5768
MEDIUM5.9
Description
A vulnerability exists in the HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Incomplete or wrong received APDU frame layout may cause blocking on link layer. Error reason was an endless blocking when reading incoming frames on link layer with wrong length information of APDU or delayed reception of data octets. Only communication link of affected HCI IEC 60870-5-104 is blocked. If attack sequence stops the communication to the previously attacked link gets normal again.
Details CVE
Score CVSS v3.15.9
SeveriteMEDIUM
Vecteur CVSSCVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H
Vecteur d'attaqueNETWORK
ComplexiteHIGH
Privileges requisNONE
Interaction utilisateurNONE
Publie12/4/2023
Derniere modification11/21/2024
Sourcenvd
Observations honeypot0
Produits affectes
hitachienergy:rtu520hitachienergy:rtu520_firmwarehitachienergy:rtu530hitachienergy:rtu530_firmwarehitachienergy:rtu540hitachienergy:rtu540_firmwarehitachienergy:rtu560hitachienergy:rtu560_firmware