← Retour aux CVEs
CVE-2023-2071
CRITICAL9.8
Description
Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. The device has the functionality, through a CIP class, to execute exported functions from libraries. There is a routine that restricts it to execute specific functions from two dynamic link library files. By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.
Details CVE
Score CVSS v3.19.8
SeveriteCRITICAL
Vecteur CVSSCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Vecteur d'attaqueNETWORK
ComplexiteLOW
Privileges requisNONE
Interaction utilisateurNONE
Publie9/12/2023
Derniere modification11/21/2024
Sourcenvd
Observations honeypot0
Produits affectes
rockwellautomation:factorytalk_viewrockwellautomation:panelview_plus
Faiblesses (CWE)
CWE-20CWE-434
References
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1140724(PSIRT@rockwellautomation.com)
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1140724(af854a3a-2127-422b-91ae-364da2661108)
Correlations IOC
Aucune correlation enregistree
This product uses data from the NVD API but is not endorsed or certified by the NVD.