TROYANOSYVIRUS
Retour aux CVEs

CVE-2023-1133

CRITICAL
9.8

Description

Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability in which the Device-status service listens on port 10100/ UDP by default. The service accepts the unverified UDP packets and deserializes the content, which could allow an unauthenticated attacker to remotely execute arbitrary code.

Details CVE

Score CVSS v3.19.8
SeveriteCRITICAL
Vecteur CVSSCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Vecteur d'attaqueNETWORK
ComplexiteLOW
Privileges requisNONE
Interaction utilisateurNONE
Publie3/27/2023
Derniere modification11/21/2024
Sourcenvd
Observations honeypot0

Produits affectes

deltaww:infrasuite_device_master

Faiblesses (CWE)

CWE-502

Correlations IOC

Aucune correlation enregistree