TROYANOSYVIRUS
Retour aux CVEs

CVE-2022-33174

CRITICAL
9.8

Description

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.

Details CVE

Score CVSS v3.19.8
SeveriteCRITICAL
Vecteur CVSSCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Vecteur d'attaqueNETWORK
ComplexiteLOW
Privileges requisNONE
Interaction utilisateurNONE
Publie6/13/2022
Derniere modification11/21/2024
Sourcenvd
Observations honeypot0

Produits affectes

powertekpdus:basic_pdupowertekpdus:basic_pdu_firmwarepowertekpdus:piml_pdupowertekpdus:piml_pdu_firmwarepowertekpdus:pm_pdupowertekpdus:pm_pdu_firmwarepowertekpdus:smart_pimpowertekpdus:smart_pim_firmwarepowertekpdus:smart_pompowertekpdus:smart_pom_firmwarepowertekpdus:smart_pomspowertekpdus:smart_poms_firmwarepowertekpdus:smart_pospowertekpdus:smart_pos_firmware

Faiblesses (CWE)

CWE-863

References

Correlations IOC

Aucune correlation enregistree

This product uses data from the NVD API but is not endorsed or certified by the NVD.