← Retour aux CVEs
CVE-2022-33174
CRITICAL9.8
Description
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
Details CVE
Score CVSS v3.19.8
SeveriteCRITICAL
Vecteur CVSSCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Vecteur d'attaqueNETWORK
ComplexiteLOW
Privileges requisNONE
Interaction utilisateurNONE
Publie6/13/2022
Derniere modification11/21/2024
Sourcenvd
Observations honeypot0
Produits affectes
powertekpdus:basic_pdupowertekpdus:basic_pdu_firmwarepowertekpdus:piml_pdupowertekpdus:piml_pdu_firmwarepowertekpdus:pm_pdupowertekpdus:pm_pdu_firmwarepowertekpdus:smart_pimpowertekpdus:smart_pim_firmwarepowertekpdus:smart_pompowertekpdus:smart_pom_firmwarepowertekpdus:smart_pomspowertekpdus:smart_poms_firmwarepowertekpdus:smart_pospowertekpdus:smart_pos_firmware
Faiblesses (CWE)
CWE-863
References
https://gynvael.coldwind.pl/?lang=en&id=748(cve@mitre.org)
https://gynvael.coldwind.pl/?lang=en&id=748(af854a3a-2127-422b-91ae-364da2661108)
Correlations IOC
Aucune correlation enregistree
This product uses data from the NVD API but is not endorsed or certified by the NVD.