TROYANOSYVIRUS
Retour aux CVEs

CVE-2013-2806

N/A

Description

Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “End of Current Record” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size.” Then the service will calculate an incorrect value for the “End of Current Record” field causing access violations that lead to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation security advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599

Details CVE

Score CVSS v3.1N/A
Publie3/26/2019
Derniere modification11/21/2024
Sourcenvd
Observations honeypot0

Produits affectes

rockwellautomation:rslinx_enterprise

Faiblesses (CWE)

CWE-190CWE-190

Correlations IOC

Aucune correlation enregistree

This product uses data from the NVD API but is not endorsed or certified by the NVD.