← Zuruck zu CVEs
CVE-2025-3498
CRITICAL9.9
Beschreibung
An unauthenticated user with management network access can get and modify the Radiflow iSAP Smart Collector (CentOS 7 - VSAP 1.20) configuration. The device has two web servers that expose unauthenticated REST APIs on the management network (TCP ports 8084 and 8086). An attacker can use these APIs to get access to all system settings, modify the configuration and execute some commands (e.g., system reboot).
CVE Details
CVSS v3.1 Bewertung9.9
SchweregradCRITICAL
CVSS VektorCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:H/A:L
AngriffsvektorNETWORK
KomplexitatLOW
Erforderliche PrivilegienNONE
BenutzerinteraktionNONE
Veroffentlicht7/9/2025
Zuletzt geandert7/10/2025
Quellenvd
Honeypot-Sichtungen0
Schwachen (CWE)
CWE-306
Referenzen
https://www.cvcn.gov.it/cvcn/cve/CVE-2025-3498(a6d3dc9e-0591-4a13-bce7-0f5b31ff6158)
IOC Korrelationen
Keine Korrelationen erfasst