TROYANOSYVIRUS
Zuruck zu CVEs

CVE-2025-1863

CRITICAL
9.8

Beschreibung

Insecure default settings have been found in recorder products provided by Yokogawa Electric Corporation. The default setting of the authentication function is disabled on the affected products. Therefore, when connected to a network with default settings, anyone can access all functions related to settings and operations. As a result, an attacker can illegally manipulate and configure important data such as measured values and settings. This issue affects GX10 / GX20 / GP10 / GP20 Paperless Recorders: R5.04.01 or earlier; GM Data Acquisition System: R5.05.01 or earlier; DX1000 / DX2000 / DX1000N Paperless Recorders: R4.21 or earlier; FX1000 Paperless Recorders: R1.31 or earlier; μR10000 / μR20000 Chart Recorders: R1.51 or earlier; MW100 Data Acquisition Units: All versions; DX1000T / DX2000T Paperless Recorders: All versions; CX1000 / CX2000 Paperless Recorders: All versions.

CVE Details

CVSS v3.1 Bewertung9.8
SchweregradCRITICAL
CVSS VektorCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
AngriffsvektorNETWORK
KomplexitatLOW
Erforderliche PrivilegienNONE
BenutzerinteraktionNONE
Veroffentlicht4/18/2025
Zuletzt geandert4/21/2025
Quellenvd
Honeypot-Sichtungen0

Schwachen (CWE)

CWE-1188

Referenzen

IOC Korrelationen

Keine Korrelationen erfasst

This product uses data from the NVD API but is not endorsed or certified by the NVD.