TROYANOSYVIRUS
Zuruck zu CVEs

CVE-2025-11783

CRITICAL
9.8

Beschreibung

Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50 v9.0.2. The vulnerability is found in the 'AddEvent()' function when copying the user-controlled username input to a fixed-size buffer (48 bytes) without boundary checking. This can lead to memory corruption, resulting in possible remote code execution.

CVE Details

CVSS v3.1 Bewertung9.8
SchweregradCRITICAL
CVSS VektorCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
AngriffsvektorNETWORK
KomplexitatLOW
Erforderliche PrivilegienNONE
BenutzerinteraktionNONE
Veroffentlicht12/2/2025
Zuletzt geandert12/3/2025
Quellenvd
Honeypot-Sichtungen0

Betroffene Produkte

circutor:sge-plc1000circutor:sge-plc1000_firmwarecircutor:sge-plc50circutor:sge-plc50_firmware

Schwachen (CWE)

CWE-121

IOC Korrelationen

Keine Korrelationen erfasst

This product uses data from the NVD API but is not endorsed or certified by the NVD.