← Zuruck zu CVEs
CVE-2023-5768
MEDIUM5.9
Beschreibung
A vulnerability exists in the HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Incomplete or wrong received APDU frame layout may cause blocking on link layer. Error reason was an endless blocking when reading incoming frames on link layer with wrong length information of APDU or delayed reception of data octets. Only communication link of affected HCI IEC 60870-5-104 is blocked. If attack sequence stops the communication to the previously attacked link gets normal again.
CVE Details
CVSS v3.1 Bewertung5.9
SchweregradMEDIUM
CVSS VektorCVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H
AngriffsvektorNETWORK
KomplexitatHIGH
Erforderliche PrivilegienNONE
BenutzerinteraktionNONE
Veroffentlicht12/4/2023
Zuletzt geandert11/21/2024
Quellenvd
Honeypot-Sichtungen0
Betroffene Produkte
hitachienergy:rtu520hitachienergy:rtu520_firmwarehitachienergy:rtu530hitachienergy:rtu530_firmwarehitachienergy:rtu540hitachienergy:rtu540_firmwarehitachienergy:rtu560hitachienergy:rtu560_firmware
Schwachen (CWE)
CWE-79
Referenzen
https://publisher.hitachienergy.com/preview?DocumentId=8DBD000176&languageCode=en&Preview=true(cybersecurity@hitachienergy.com)
https://publisher.hitachienergy.com/preview?DocumentId=8DBD000176&languageCode=en&Preview=true(af854a3a-2127-422b-91ae-364da2661108)
IOC Korrelationen
Keine Korrelationen erfasst
This product uses data from the NVD API but is not endorsed or certified by the NVD.