← Zuruck zu CVEs
CVE-2023-2071
CRITICAL9.8
Beschreibung
Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. The device has the functionality, through a CIP class, to execute exported functions from libraries. There is a routine that restricts it to execute specific functions from two dynamic link library files. By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.
CVE Details
CVSS v3.1 Bewertung9.8
SchweregradCRITICAL
CVSS VektorCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
AngriffsvektorNETWORK
KomplexitatLOW
Erforderliche PrivilegienNONE
BenutzerinteraktionNONE
Veroffentlicht9/12/2023
Zuletzt geandert11/21/2024
Quellenvd
Honeypot-Sichtungen0
Betroffene Produkte
rockwellautomation:factorytalk_viewrockwellautomation:panelview_plus
Schwachen (CWE)
CWE-20CWE-434
Referenzen
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1140724(PSIRT@rockwellautomation.com)
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1140724(af854a3a-2127-422b-91ae-364da2661108)
IOC Korrelationen
Keine Korrelationen erfasst
This product uses data from the NVD API but is not endorsed or certified by the NVD.